Anti-Static Applications
Clause 7.4 of EN60079-0 refers to the avoidance of a
build-up of electrostatic charge on Group I or Group II
electrical equipment. Electrical equipment shall be so
designed that under normal conditions of use,
maintenance and cleaning, danger of ignition due to
electrostatic charges shall be avoided. This
requirement is satisfied by suitable selection of the
material so that surface resistance complies with either
of the limits given below when
measured in accordance with 26.13;
10
9
Ω
measured at (50 ± 5) %
relative humidity; or 10"
Ω
measured
at (30 ± 5) % relative humidity.
Flexicon have two ranges of anti-
static performance coated liquid
tight systems.
Hazardous Area Approvals - EXD now featuring Group 1 approvals
The following table provides further information and details on our ATEX, IECEx and GOST
approvals for our straight EXD glands.
Group I
ATEX APPROVAL to EN60079-0 2009 Sira Certificate no:
Sira 10ATEX1172X
Ex d Flameproof
Ex d I Mb
EN 60079-1 2007
Ex e Increased Safety
Ex e I Mb
EN 60079-7 2007
IECEx APPROVAL to IEC60079-0 2007 Sira Certificate no: IECEx SIR 10.0094X
Ex d Flameproof
Ex d I Mb
IEC 60079-1 2007
Ex e Increased Safety
Ex e I Mb
IEC 60079-7 2006-7
Group II
ATEX APPROVAL to EN60079-0 2009 Sira Certificate no:
Sira 10ATEX1172X
Ex d Flameproof
Ex d II C Gb
EN 60079-1 2007
Ex e Increased Safety
Ex e II C Gb
EN 60079-7 2007
Ex ta Dust Ignition Proof
Ex ta IIIC DA IP6X IEC 60079-31 2008
IECEx APPROVAL to IEC60079-0 2007 Sira Certificate no: IECEx SIR 10.0094X
Ex d Flameproof
Ex d II C Gb
IEC 60079-1 2007
Ex e Increased Safety
Ex e II C Gb
IEC 60079-7 2006-7
Ex ta Dust Ignition Proof
Ex ta IIIC DA IP6X IEC 60079-31 2008
GOST APPROVAL no.
POCC GB.HO06.B00207
Why Use Conduit Over Cable?
In summary, using a Flexicon conduit system with our EXD barrier glands or EXE fittings can provide the following benefits over cable:
•
Simplified termination and
greater enclosure integrity
•
Reduced installation time
- less terminations
•
Cable is mechanically
protected
KG
•
No need for
specialist cables
£'s
•
Flameproof integrity
with EXD glands
•
Can provide EMC screening
(braided versions)
•
No need for use
of SWA cables
SWA
•
Future proofing the installation
- easier to upgrade
•
Increased safety and Dust ignition
protection with EXE fittings
LTPPU/LTPPUAS
LTPSS
LTBRDP
LTBRDLFH
LTPBRD
STANDARD
EMC
SCREEN
ENHANCED
EMC
SCREEN
SUPER
EMC
SCREEN
STANDARD
EMC
SCREEN
ENHANCED
EMC
SCREEN
SUPER
EMC
SCREEN
STANDARD
LOW FIRE
HAZARD
EXTRA
LOW FIRE
HAZARD
INHERENT
LOW FIRE
HAZARD
STANDARD
EMC
SCREEN
ENHANCED
EMC
SCREEN
SUPER
EMC
SCREEN
EXD Barrier Glands
EXD Accessories
EXE Fittings
13
See Pg 68, 69 & 70
See Pg 72 & 73
See Pg 71
See page 71 for information on EXE gland approvals
Ex e
Ex tb