Anti-Static Applications

Clause 7.4 of EN60079-0 refers to the avoidance of a

build-up of electrostatic charge on Group I or Group II

electrical equipment. Electrical equipment shall be so

designed that under normal conditions of use,

maintenance and cleaning, danger of ignition due to

electrostatic charges shall be avoided. This

requirement is satisfied by suitable selection of the

material so that surface resistance complies with either

of the limits given below when

measured in accordance with 26.13;

10

9

Ω

measured at (50 ± 5) %

relative humidity; or 10"

Ω

measured

at (30 ± 5) % relative humidity.

Flexicon have two ranges of anti-

static performance coated liquid

tight systems.

Hazardous Area Approvals - EXD now featuring Group 1 approvals

The following table provides further information and details on our ATEX, IECEx and GOST

approvals for our straight EXD glands.

Group I

ATEX APPROVAL to EN60079-0 2009 Sira Certificate no:

Sira 10ATEX1172X

Ex d Flameproof

Ex d I Mb

EN 60079-1 2007

Ex e Increased Safety

Ex e I Mb

EN 60079-7 2007

IECEx APPROVAL to IEC60079-0 2007 Sira Certificate no: IECEx SIR 10.0094X

Ex d Flameproof

Ex d I Mb

IEC 60079-1 2007

Ex e Increased Safety

Ex e I Mb

IEC 60079-7 2006-7

Group II

ATEX APPROVAL to EN60079-0 2009 Sira Certificate no:

Sira 10ATEX1172X

Ex d Flameproof

Ex d II C Gb

EN 60079-1 2007

Ex e Increased Safety

Ex e II C Gb

EN 60079-7 2007

Ex ta Dust Ignition Proof

Ex ta IIIC DA IP6X IEC 60079-31 2008

IECEx APPROVAL to IEC60079-0 2007 Sira Certificate no: IECEx SIR 10.0094X

Ex d Flameproof

Ex d II C Gb

IEC 60079-1 2007

Ex e Increased Safety

Ex e II C Gb

IEC 60079-7 2006-7

Ex ta Dust Ignition Proof

Ex ta IIIC DA IP6X IEC 60079-31 2008

GOST APPROVAL no.

POCC GB.HO06.B00207

Why Use Conduit Over Cable?

In summary, using a Flexicon conduit system with our EXD barrier glands or EXE fittings can provide the following benefits over cable:

Simplified termination and

greater enclosure integrity

Reduced installation time

- less terminations

Cable is mechanically

protected

KG

No need for

specialist cables

£'s

Flameproof integrity

with EXD glands

Can provide EMC screening

(braided versions)

No need for use

of SWA cables

SWA

Future proofing the installation

- easier to upgrade

Increased safety and Dust ignition

protection with EXE fittings

LTPPU/LTPPUAS

LTPSS

LTBRDP

LTBRDLFH

LTPBRD

STANDARD

EMC

SCREEN

ENHANCED

EMC

SCREEN

SUPER

EMC

SCREEN

STANDARD

EMC

SCREEN

ENHANCED

EMC

SCREEN

SUPER

EMC

SCREEN

STANDARD

LOW FIRE

HAZARD

EXTRA

LOW FIRE

HAZARD

INHERENT

LOW FIRE

HAZARD

STANDARD

EMC

SCREEN

ENHANCED

EMC

SCREEN

SUPER

EMC

SCREEN

EXD Barrier Glands

EXD Accessories

EXE Fittings

13

See Pg 68, 69 & 70

See Pg 72 & 73

See Pg 71

See page 71 for information on EXE gland approvals

Ex e

Ex tb